5 Water Loss Mistakes to Avoid

In the United States we are expecting long-term water shortages.

Between city growth, new data center development, and leaking waterlines we have a crisis emerging. We desperately need every gallon, but at the time of our greatest need we are still losing around 20% of our drinking water into the ground. AWWA’s 2026 State of the Water Industry survey found 33% of utilities rate their long-term supply as “borderline.”

Most city managers, utility leaders, and utility operators want to solve this issue. However, it can be very complex and expensive to find and fix the pipeline leaks. There are multiple ways we track water losses as an industry. From bad meters, to pipeline leaks, to theft, we have so many ways to lose water.

We need to solve these issues today, not wait 5 more years for them to get even worse.

Below are five common mistakes people make when trying to solve their water loss issue.

1. Reporting as a Percentage vs. per Connection

The national guide on tracking water loss and non-revenue water, American Water Works Association Technical Manual M36, revised the standard in 2016 to track in terms of gallons of loss per connection per day. AWWA took percentage indicators out of the fifth edition of Manual M36 and out of version 6.0 of its Free Water Audit Software, calling them “imprecise, misleading, and not actionable.” This is because if you just sell less water in a year but the water leaks are the same, you see an odd scenario where your customers conserved more water but on a % basis your losses went up.

This is a more accurate way of tracking losses for the system based on the connections and size vs. just the total volume. The regulations for losses vary. In Texas the threshold is 30 (urban) or 57 (rural) gallons of loss per connection per day.

2. Not Auditing the Billing Data

Just as an example, one utility’s billing system showed over 561 million gallons of consumption. However, once duplicate records were checked and removed, the total gallons dropped to 516 million gallons. We see this in many systems: the billing system has errors, omissions, manual overrides, and data gaps that may lead a utility to have a false sense of their monthly water demands.

It’s important to go to the raw data generated by the metering system, not the changed version. So when looking at your utility water consumption, figure out how to access the original data and use that for reporting.

In this example, 45 million gallons, or 8% of reported consumption, were duplicate records. Each of those data issues reflected actual gallons of water. About 123,000 gallons a day the utility wasn’t tracking. Other common billing distortions include estimated reads posted as actual, zero reads from dead meters or radios, manual overrides, and accounts missing from billing entirely. At one utility we assessed, zero-billed and estimated bills had climbed above 10%, well above the industry benchmark of 0.6%.

3. Not Testing Production Meters

The production meters are just after the water plant and before the water distribution system. Older meters can lose accuracy of 0.5% to 2% a year. It’s important to test critical meters on an annual or quarterly basis to make sure you know exactly how much water is entering your system. A 2% error at a 10 MGD plant is 200,000 gallons a day, or 73 million gallons a year.

Just doing a test isn’t enough; it is critical to make sure of the testing method being used. We have seen many temporary measures for testing and non-standard testing certifications. Your utility must follow the AWWA meter testing requirements and guidance for best results. Otherwise you run the risk of mismanaging large amounts of water.

A proper production meter test has four steps:

  1. Electronically check or calibrate the transmitter and confirm its signal matches SCADA.
  2. Run an in-place flow test against a recently calibrated reference: a Pitot traverse, insertion meter, or clamp-on ultrasonic meter.
  3. Calculate the volume-weighted error and compare it to a ±3% target.
  4. Repair or recalibrate, document the results, and apply the error adjustment in your water audit.
4. Not Testing the Customer Meters

We see this at many utilities, as new meters can be expensive, in the $200–400 range! So they may defer replacing older meters and get the additional use and life out of the old ones. This can be a very expensive mistake. Older-style mechanical meters are fairly accurate for the first 8–12 years of life and then begin to degrade in accuracy, up to 2% a year.

There are so many variables that impact meter health. The water quality: hard water can cause scaling faster than soft water. The high and low flows can wear out the mechanical parts. Long periods of no usage. High pressure spikes can damage the rotating components. Some meters can quickly lose accuracy at your utility, others may last decades. The only way to know is through actual testing in your utility.

So your 16-year-old meter may be under-counting by 10–20% a year. On an average water bill of $530 a year, that comes out to $53–106 a year!

5. Tracking Only 1x a Year

If your water losses are low, under 20 gallons per connection a day, then annual tracking can make sense. However, most systems are well above those limits and should be doing monthly water loss tracking. This enables the utility to see exactly what months they have higher losses and detect failing meters or breaking pipes that same month, not just in January when they update numbers for the year.

Different states have varying requirements for reporting on water losses. Every utility that has a capacity limitation, older pipelines or meters, and limited funding needs to be tracking this each month to prevent any nasty surprises at the end of the year.

Another problem from only tracking once a year is our memories can falter. There may be a good reason, such as new construction or a fiber contractor breaking multiple waterlines in March, but if you wait until the next year to add up all the water losses you can miss the true reasons.

InfraSync Ray: monthly water balance by AWWA category for selected district metered areas.

Water loss is typically complex, and the real issues require good data and a team that understands the meters, the data systems, and the water utility. Looking at specific issues in isolation can give a false sense of where the real problems are. At InfraSync we provide water loss audits, validations, and set up reliable testing systems so you can KNOW, not just assume, where your real problems are as a utility.

Get help from InfraSync to find your water loss and fix your system capacity


About Infrasync: Infrasync helps water utilities modernize operations through smart technology implementation and data-driven decision-making. We partner with utility leaders to identify constraints, implement solutions, and measure results, transforming complexity into clarity.


 

Learn More Now - Knowledge is Power, get in touch with a Smart Utility Engineer for an Assessment

Contact Us

Contact us

contact us Get your comprehensive smart utility assessment Physical Infrastructure Performance + Digital Infrastructure Architecture + Performance Benchmarking against industry standards + A strategic roadmap

Read More »